Fieldbus KT-MB-GT2AD.FF Pepperl+Fuchs 239818
Fieldbus KT-MB-GT2AD.FF Pepperl+Fuchs 239818

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

KT-MB-GT2AD.FF 239818 Pepperl+Fuchs Fieldbus

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KT-MB-GT2AD.FF

Part number

239818

Type

Fieldbus

Description

  • System integration kit for Advanced Diagnostics
  • PCS integration via Diagnostic Manager or device DTM
  • Simple automatic setup of Advanced Diagnostics
  • Common alarm handling
  • For FOUNDATION Fieldbus and PROFIBUS PA
  • Installation in Zone 2

Stock availability:

On request

1005.7 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KT-MB-GT2AD.FF 239818

The FieldConnex ® Diagnostic Gateway is the interface between stationary Advanced Diagnostic Modules (ADM) and the control system. It offers access to all ADM data in two ways: via Ethernet and the Diagnostic Manager software or via FOUNDATION Fieldbus H1 and DTM/EDD or both. The gateway configures itself and automatically detects the ADMs. The Diagnostic Manager automatically finds gateways on the same subnet. The setup of the diagnostic bus and all connected modules is automatic. This significantly simplifies engineering of FieldConnex ® Advanced Diagnostics.

Features KT-MB-GT2AD.FF 239818

General specifications
Design / MountingMotherboard based
Supply
Rated voltage19.2 ... 35 V DC SELV/PELV
Rated current120 ... 70 mA
Power dissipationmax. 2.5 W
Fieldbus interface
Fieldbus typeFOUNDATION Fieldbus
Physical layer profileprofile type 114
ITK version6
Implementationresource block1x RS function block4x MDI, 1x MDO, 1x MAI, 1x DI transducer block16x ADM TB, 1x IO TB
Firmware updateEthernet
Polaritypolarity-sensitive
Rated voltage9 ... 35 V SELV/PELV
Rated current0 mA
Ethernet Interface
Port100 BASE-TX
ProtocolTCP/IP and UDP/IP
ServicesICMP , DHCP , AutoIP , HTTP
Connection typeRJ-45 socket, 8-pin
Transfer rate100 MBit/s
Diagnostic Bus
Number of Diagnostic Bus Channels2
Number of Diagnostic Modules/Channel31 Using Ethernet Interface , 8 Using Fieldbus Interface
Terminationintegrated
Cable length/Channel30 m
Indicators/operating means
LED ERRred: Hardware fault
LED PWRgreen: Power on
LINK/ACTyellow
CH1, CH2yellow: diagnostic bus activity
Outputs
Output Ialarm output diagnostic bus channel 1 , volt-free contact , NC contact
Voltage50 V DC
Currentmax. 1 A
Output IIalarm output diagnostic bus channel 2 , volt-free contact , NC contact
Voltage50 V DC
Currentmax. 1 A
Output IIIcommon alarm , volt-free contact , NC contact
Voltage50 V DC
Currentmax. 1 A
Galvanic isolation
All circuits/FEfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output I, II/other circuitsfunctional insulation acc. to IEC 62103, rated insulation voltage 250 Veff
Ethernet/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Ethernet/other circuitsfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus/other circuitsfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Diagnostic Bus/other circuitsfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Low voltage
Directive 73/23/EECEN 61010
Standard conformity
Galvanic isolationIEC 62103
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Climatic conditionsDIN IEC 721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
EthernetIEEE 802.3
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F) hazardous area -40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Housing materialPolycarbonate
Housing widthsee dimensions
Housing heightsee dimensions
Housing depthsee dimensions
Degree of protectionIP20
Mass470 g
MountingDIN rail mounting
Data for application in connection with hazardous areas
CertificateTÜV 14 ATEX 115980 X
Marking II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
IECEx approvalIECEx TUN 14.0003X
Approved forEx nA IIC T4 Gc