Description

AS-Interface sensor/actuator module VBA-4E4A-G12-XEL

Stock availability:

On request

202.14 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VBA-4E4A-G12-XEL 228643

The VBA-4E4A-G12-XEL is an AS-Interface trigger module with 4 inputs and 4 outputs. 2- and 3-wire sensors as well as mechanical contacts can be connected to the plus switching electronic inputs. The outputs are electronic outputs which can be energized with max. 24 V DC and 1 A per output. The solid housing permits fast mounting without tools as well as easy removal without tools. The stainless steel shell and the cast housing ensure durability and a high protection category. The connection to the AS-Interface calbe and to the external power supply is achieved via penetration technology in the integrated flat cable. The insert for the flat cables can be turned in two orientations. All connections to inputs and outputs are implemented via metal inserts for high stability. The connection to the sensors/actuators is achieved via a M12 x 1 circular connector with SPEEDCON quick locking option. The inputs and the connected sensors as well as the outputs and the connected actuators are supplied via an external power source (AUX). To indicate the current switching state there is an LED for each input fitted to the top of the module. An LED to indicate the AS-Interface voltage and that the module has an address of 0 is available, another indicates errors in the AS-Interface communication as well as periphery faults. Another LED indicates the external power supply (AUX). This module can be mounted in any position using three screws or can be snapped onto the DIN rail using the stainless steel holder. An output overload is reported to the AS-Interface master via the function periphery fault. The communcation with the AS-Interface remains intact.

Features VBA-4E4A-G12-XEL 228643

Product Description
G12 flat module 4 inputs (PNP) and 4 electronic outputs
General specifications
Slave typeA/B slave
AS-Interface specificationV3.0
Required master specification&ge, V3.0
UL File NumberE223772
Indicators/operating means
LED FAULTerror display, LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs
LED PWRAS-Interface voltage, green LED green: voltage OK flashing green: address 0
LED AUXext. auxiliary voltage UAUX, dual LED green/red green: voltage OK red: reverse voltage
LED INswitching state (input), 4 LED yellow
Electrical specifications
Auxiliary voltage24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current&le, 40 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom external auxiliary voltage UAUX
Current loading capacity&le, 500 mA overload and short-circuit resistant
Input current&le, 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)&le, 2 mA
1 (attenuated)&ge, 6 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Current1 A per output
Voltage&ge, (UAUX - 0.5 V)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
Programming instructions
ProfileS-7.A.7
IO code7
ID codeA
ID1 code7
ID2 code7
Data bits (function via AS-Interface) input output
D0 IN1 OUT1
D1 IN2 OUT2
D2 IN3 OUT3
D3 IN4 OUT4
Parameter bits (programmable via AS-i)function
P0communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
P1Input filter P1 = 0 input filter on, pulse suppression &le, 2 ms P1 = 1 input filter off (default settings)
P2Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
P3not used
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude&le, 2000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree3
Mechanical specifications
Degree of protectionIP67
ConnectionCable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector
Material
HousingPBT
Mass200 g
Tightening torque, cable gland0.4 Nm