We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.
Manufacturer
Pepperl+Fuchs
Country
Germany
Name
VBA-4E-G12-ZAL
Part number
200505
Type
Module
Description
AS-Interface sensor module VBA-4E-G12-ZAL
Stock availability:
On request
Product Description |
---|
G12 flat module 4 inputs (PNP) |
General specifications | ||
---|---|---|
Slave type | A/B slave | |
AS-Interface specification | V3.0 | |
Required master specification | &ge, V2.1 | |
UL File Number | E223772 | |
Functional safety related parameters | ||
MTTFd | 330 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Indicators/operating means | ||
LED FAULT | error display, LED red red: communication error or address is 0 red flashing: overload of sensor supply | |
LED PWR | AS-Interface voltage, green LED green: voltage OK flashing green: address 0 | |
LED AUX | ext. auxiliary voltage UAUX, dual LED green/red green: voltage OK red: reverse voltage | |
LED IN | switching state (input), 4 LED yellow | |
Electrical specifications | ||
Auxiliary voltage | 24 V DC ± 15 % PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | &le, 40 mA | |
Protection class | III | |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral | |
Input | ||
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC | |
Supply | from external auxiliary voltage UAUX | |
Current loading capacity | &le, 600 mA overload and short-circuit resistant | |
Input current | &le, 8 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 (Type 2) | |
0 (unattenuated) | &le, 2 mA | |
1 (attenuated) | &ge, 6 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Input | EN 61131-2 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005 EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-0.A.2 | |
IO code | 0 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 2 | |
Data bits (function via AS-Interface) | input output | |
D0 | IN1 - | |
D1 | IN2 - | |
D2 | IN3 - | |
D3 | IN4 - | |
Parameter bits (programmable via AS-i) | function | |
P0 | not used | |
P1 | Input filter P1 = 0 input filter on, pulse suppression &le, 2 ms P1 = 1 input filter off (default settings) | |
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) | |
P3 | not used | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | &le, 2000 m above MSL | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks | |
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Pollution degree | 3 | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Connection | cable piercing method flat cable yellow inputs: M12 round connector | |
Material | ||
Housing | PBT | |
Mass | 200 g | |
Tightening torque, cable gland | 0.4 Nm | |
Mounting | Mounting plate |