Gateway VBG-DN-K20-DMD Pepperl+Fuchs 190325
Gateway VBG-DN-K20-DMD Pepperl+Fuchs 190325

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

VBG-DN-K20-DMD 190325 Pepperl+Fuchs Gateway

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

VBG-DN-K20-DMD

Part number

190325

Type

Gateway

Description

  • Gateway compliant with AS-Interface specification 3.0
  • 2 AS-Interface networks
  • Dublicate addressing detection
  • Earth fault detection
  • AS-Interface noise detection
  • Easy commissioning by graphic display
  • Commissioning, locally on the gateway or via AS-i Control Tools software
  • Fault diagnosis via LEDs and grafic display
  • AS-Interface monitor or extended AS-Interface diagnostic read via display
  • Ethernet diagnostic interface

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VBG-DN-K20-DMD 190325

The VBG-DN-K20-DMD is a DeviceNet gateway with two AS-Interface masters compliant with AS-Interface specification 3.0. The variant in an IP20 stainless steel housing is particularly suitable for use in the switching cabinet for snapping onto 35mm mounting rails. The gateway is a 100% DeviceNet slave (group 2 slave) and, as a listed product, directly addressable through the DeviceNet device manager. Communication between the ASInterface and DeviceNet is implemented by the gateway with no additional programming effort. For the AS-Interface gateway with graphic display, the commissioning of the AS-Interface circuit as well as the test of the connected periphery can be completely separated from the commissioning of the DeviceNet as well as the programming. On-site operation using the graphical display and the four buttons make it possible to perform all functions on the display. Address assignment and transfer of the expected configuration can be done with the buttons. There are 7 LEDs on the front panel, showing the current status of the AS-i line. An additional RS 232 socket is available with the option to read out data directly from the gateway via gateway, network and function within the scope of an enhanced on-site diagnosis. Using the AS-i Control Tools package (not included), many functions can be remotely controlled via PC. The gateway draws its power from the AS-interface cable. The connection of the AS-Interface gateway to the DeviceNet uses the 5pin CombiCon plug according to the DeviceNet specification. There are self-opening device terminals available for all other connections. PLC Functionality Furthermore, the gateway can optionally be delivered with PLC functionality. Therefor you can order a code key VAZ-CTR additionally.

Features VBG-DN-K20-DMD 190325

Product Description
DeviceNet Gateway, double master for 2 AS-Interface networks
General specifications
AS-Interface specificationV3.0
PLC-Functionalityactivateable
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
UL File NumberE223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Indicators/operating means
DisplayIlluminated graphical LC display for addressing and error messages
LED AS-i ACTIVEAS-Interface operation normal, LED green
LED CONFIG ERRconfiguration error, LED red
LED PRG ENABLEautom. programming, LED green
LED POWERvoltage ON, LED green
LED PRJ MODEprojecting mode active, LED yellow
LED U AS-iAS-Interface voltage, LED green
LED MNSModule/net status, LED green/red
Switch SETSelection and setting of a slave address
OK buttonMode selection traditional-graphical/confirmation
Button MODEMode selection PRJ-operation/save configuration/cursor
ESC buttonMode selection traditional-graphical/cancel
Electrical specifications
Insulation voltage&ge, 500 V
Rated operating voltagefrom AS-Interface
Rated operating current&le, 200 mA from AS-Interface circuit 1 &le, 70 mA from AS-Interface circuit 2
Interface 1
ProtocolDeviceNet
Interface 2
Interface typeRS 232, serial Diagnostic Interface
Transfer rate19,2 kBit/s
Connection
AS-Interfacespring terminals, removable
DeviceNet5-pin CombiCon connector according to DeviceNet specification
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-6-4:2001, EN 50295:1999
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Approvals and certificates
EAC conformityTR CU 020/2011
UL approvalAn isolated source with a secondary open circuit voltage of &le, 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Mass520 g
Construction typeLow profile housing , Stainless steel