Stock availability:
On request
Product Description |
---|
G20 module for digital inputs/outputs, 4 inputs and 3 outputs |
General specifications | ||
---|---|---|
Slave type | A/B slave | |
AS-Interface specification | V3.0 | |
Required master specification | &ge, V2.1 | |
UL File Number | E223772 For use in NFPA 79 Applications only | |
MTBF | 110 a | |
Indicators/operating means | ||
LED FAULT | error display, LED red red: communication error or address is 0 red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing | |
LED PWR | AS-Interface voltage, green LED green: voltage OK flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing | |
LED AUX | ext. auxiliary voltage UAUX, dual LED green/red green: voltage OK red: reverse voltage | |
LED IN | switching state (input), 4 LED yellow | |
LED OUT | Switching state (output), 3 LED yellow | |
Electrical specifications | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | &le, 35 mA | |
Input | ||
Number/Type | 4 Inputs for 3-wire sensors (PNP), DC | |
Supply | from external auxiliary voltage UAUX | |
Current loading capacity | 500 mA , overload and short-circuit protected | |
Input current | &le, 8 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 0 (undamped) &le, 0.5 mA 1 (damped) &ge, 2.0 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Output | ||
Number/Type | 3 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from external auxiliary voltage UAUX | |
Voltage | &ge, (UAUX - 0.5 V) | |
Current | 2 A per output TB &le, 40 °C: 6 A total TB &le, 60 °C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Input | EN 61131-2:2007 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.A.E | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | E | |
Data bits (function via AS-Interface) | input output | |
D0 | IN1 OUT1 | |
D1 | IN2 OUT2 | |
D2 | IN3 OUT3 | |
D3 | IN4 - | |
Parameter bits (programmable via AS-i) | function | |
P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) | |
P1 | Input filter P1 = 0 input filter on, pulse suppression &le, 2 ms P1 = 1 input filter off (default settings) | |
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) | |
Ambient conditions | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP54 according to EN 60529 | |
Connection | AS-Interface, AUX: Insulation piercing technology Yellow flat cable/black flat cable Inputs/outputs: M12 round plug connector in accordance with EN 61076-2-101 Inputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar Outputs: LF type (4-pin, bushing contacts, screw lock, A-coded) Matching connector: LM type or similar | |
Mass | 260 g | |
Mounting | 2 clips with &empty, 8 mm drill hole | |
Cable length | 0.7 m (Inputs) , 1.5 m (X1, X2) | |
Note | The flat cable routing is designed for 100 actuation cycles |