We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.
Manufacturer
Pepperl+Fuchs
Country
Germany
Name
VBA-4A-KE5-IJL/UJL
Part number
290768
Type
Module
Description
Stock availability:
On request
Product Description |
---|
Switch cabinet module Four analog outputs |
General specifications | ||
---|---|---|
Slave type | Standard slave | |
AS-Interface specification | V3.0 | |
Required master specification | &ge, V2.1 | |
UL File Number | E223772 | |
MTBF | 115 a | |
Indicators/operating means | ||
LED FAULT | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault | |
LED INT | Internal output voltage active, green LED | |
LED PWR | AS-Interface voltage, green LED Green: voltage OK Flashing green: address 0 or peripheral error | |
LED AUX | ext. auxiliary voltage UAUX, dual LED green/red green: voltage OK red: reverse voltage | |
LED OUT | Status of output signal, yellow LED Yellow: Output value within range Yellow flashing: lead breakage (on current output) or output value out of range | |
Electrical specifications | ||
Auxiliary voltage (output) | 24 V DC ± 15 % PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | &le, 75 mA (without outputs) / max. 200 mA | |
Protection class | III | |
Current consumption | IAUX &le, 650 mA | |
Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) | |
Output | ||
Number/Type | 4 analog outputs Current: 0 ... 20 mA Voltage: 0 ... 10 V | |
Supply | From AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX) | |
Load | voltage output: min. 1 k&Omega, current output: max. 600 &Omega, | |
Current loading capacity | &le, 100 mA (signal current + actuator power supply) from AS-Interface, overload-proof and short-circuit proof &le, 600 mA (signal current + actuator power supply) from external auxiliary voltage UAUX, overload-proof and short-circuit proof | |
Resolution | Voltage output: 3 mV Current output: 6 µ,A | |
Accuracy | 0.15 % of full-scale value | |
Temperature influence | 1 µ,A/K or 0,3 mV/K | |
Short-circuit current | voltage output: max. 22 mA | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.3.6 | |
IO code | 7 | |
ID code | 3 | |
ID1 code | F | |
ID2 code | 6 | |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. | |
Parameter bits (programmable via AS-i) | function | |
P0 | Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive | |
P1 | Output mode: P1=1 (default), 4x current outputs P1=0, 4x voltage outputs | |
P2 | Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported | |
P3 | Automatic mode: P3=1 (default), manual setting of output mode P3=0, automatic load detection (mixed mode possible) | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | &le, 2000 m above MSL | |
Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 | |
Material | ||
Housing | PA 66-FR | |
Mass | 110 g | |
Mounting | DIN mounting rail | |
Note | Max. length of jumpers = 5 cm |