VBA-4A-KE5-IJL/UJL 290768 Pepperl+Fuchs Module

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

VBA-4A-KE5-IJL/UJL

Part number

290768

Type

Module

Description

  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Power supply of outputs external or from the module, as required
  • Function indicator for the bus, external auxiliary voltage, internal output voltage, and outputs

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VBA-4A-KE5-IJL/UJL 290768

The AS-Interface connecting module VBA-4A-KE5-IJL/UJL is a switch cabinet module with 4 analog outputs. The housing is only 19 mm wide and takes up little space in the switch cabinet. The module is mounted by snapping it onto the 35 mm DIN rail in compliance with EN 50022. The connection is made via removable 4-pin push-in terminal blocks. For AS-i+, AS-i-, AUX+, and AUX-, two connections are available in each case, these connections are bridged in the terminal block. If the terminal block is disconnected from the module, the link between these connections is retained. The terminal blocks are mechanically coded. The supply to the outputs and the connected actuators can be fed either from the internal supply of the module from the AS-Interface or via the external UAUX voltage source. A switch located on the side of the module changes the source. The internal output supply is displayed via the INT LED. The relevant OUT LED displays the current switching status of the outputs. The OUT LEDs also indicate a lead breakage or an output value outside of the value range of the output. Notes: The device is equipped with a communication monitor, which sets the outputs to zero if the AS-Interface does not communicate with the module for more than 40 ms. The communication monitor can be deactivated via the parameter P0. The output mode of current or voltage output is configured via the parameters P1 and P3 or via the terminals CON1 and CON2. A wire break at the current output, an output value outside of the value range, or an overload of the actuator supply cause a peripheral fault. The parameter P2 determines whether a peripheral fault is reported to the AS-Interface master. The communication via AS-Interface remains unaffected. If an overload occurs on the actuator supply, the outputs are set to zero.

Features VBA-4A-KE5-IJL/UJL 290768

Product Description
Switch cabinet module Four analog outputs
General specifications
Slave typeStandard slave
AS-Interface specificationV3.0
Required master specification&ge, V2.1
UL File NumberE223772
MTBF115 a
Indicators/operating means
LED FAULTFault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault
LED INTInternal output voltage active, green LED
LED PWRAS-Interface voltage, green LED Green: voltage OK Flashing green: address 0 or peripheral error
LED AUXext. auxiliary voltage UAUX, dual LED green/red green: voltage OK red: reverse voltage
LED OUTStatus of output signal, yellow LED Yellow: Output value within range Yellow flashing: lead breakage (on current output) or output value out of range
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current&le, 75 mA (without outputs) / max. 200 mA
Protection classIII
Current consumptionIAUX &le, 650 mA
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Output
Number/Type4 analog outputs Current: 0 ... 20 mA Voltage: 0 ... 10 V
SupplyFrom AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX)
Loadvoltage output: min. 1 k&Omega, current output: max. 600 &Omega,
Current loading capacity&le, 100 mA (signal current + actuator power supply) from AS-Interface, overload-proof and short-circuit proof &le, 600 mA (signal current + actuator power supply) from external auxiliary voltage UAUX, overload-proof and short-circuit proof
ResolutionVoltage output: 3 mV Current output: 6 µ,A
Accuracy0.15 % of full-scale value
Temperature influence1 µ,A/K or 0,3 mV/K
Short-circuit currentvoltage output: max. 22 mA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.3.6
IO code7
ID code3
ID1 codeF
ID2 code6
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P0Watchdog: P0=1 (default), watchdog active P0=0, watchdog inactive
P1Output mode: P1=1 (default), 4x current outputs P1=0, 4x voltage outputs
P2Indication of peripheral fault: P2=1 (default), peripheral fault is reported P2=0, peripheral fault is not reported
P3Automatic mode: P3=1 (default), manual setting of output mode P3=0, automatic load detection (mixed mode possible)
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude&le, 2000 m above MSL
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree2
Mechanical specifications
Degree of protectionIP20
ConnectionRemovable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass110 g
MountingDIN mounting rail