Capacitive sensor CJ4-12GK-N-Y235563 Pepperl+Fuchs 235563
Capacitive sensor CJ4-12GK-N-Y235563 Pepperl+Fuchs 235563

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

CJ4-12GK-N-Y235563 235563 Pepperl+Fuchs Capacitive sensor

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

CJ4-12GK-N-Y235563

Part number

235563

Type

Capacitive sensor

Description

Capacitive sensor CJ4-12GK-N-Y235563

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications CJ4-12GK-N-Y235563 235563

If you are inspecting Pepperl+Fuchs CJ4-12GK-N-Y235563 235563, communicate with FAMAGA, the world's key provider of manufacturing equipment. Our company has operated for more than ten years - these are ages of experience, which are represented in the quality of spare parts and particular attention to each buyer. We cherish everyone, who liased with us - hence, our regular clients get the most attractive purchase forms and discounts on the machine made streamlined equipment market. Nowadays, there are more than 3500 such purchasers, and we constantly arrange new agreements. More than 750 affairs are settled per day, because FAMAGA supplies all over the globe . A well-shaped logistics chains and a partnership network cheer us to deliver our goods anywhere in the globe with no delay without damaging product quality.

A particular source of pride for FAMAGA is its staff members, each of whom contributes to our work. We call into our team only specialists, who already have experience in the direction of factory-made equipment.

All outcomes from FAMAGA are ensured - we are responsible for the result of our work. Now, more than 10 million units of products have been provided, and this bulk is rising every day. We are pleased that buyers choose FAMAGA again and again, and we are glad to make more progressive and technologically modern industrial equipment so as keep on top of it.

To inquire or order, phone us or write a message to the online chat on our official website. You can also forward a list of the desirable equipment to the email of firm - we will contact you ourselves with a worked out commercial proposal from FAMAGA.

Features CJ4-12GK-N-Y235563 235563

General specifications
Switching functionNormally open (NO)
Output typeNAMUR
Rated operating distance4 mm
Installationnon-flush
Assured operating distance0 ... 2.88 mm
Output type2-wire
Nominal ratings
Installation conditions
A20 mm
B80 mm
C12 mm
F70 mm
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Operating voltage7 ... 12 V
Switching frequency0 ... 1 Hz
Current consumption
Measuring plate not detected&le, 1 mA
Measuring plate detected&ge, 2.4 mA
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007 IEC 60947-5-2:2007
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typecable PVC , 55 mm with Connector, 99-3431-216-04, Binder
Core cross-section0.34 mm2
Housing materialPBT
Sensing facePBT
Degree of protectionIP68
Cable
Bending radius> 10 x cable diameter
Equipment protection level Ga
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeCJ4-12GK-N...
Effective internal capacitancemax. 60 nF , a cable length of 10 m is considered.
Effective internal inductancenegligibly small A cable length of 10 m is considered.
Highest permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeCJ4-12GK-N...
Effective internal capacitancemax. 60 nF , a cable length of 10 m is considered.
Effective internal inductancenegligibly small A cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeCJ4-12GK-N...
Effective internal capacitancemax. 60 nF , a cable length of 10 m is considered.
Effective internal inductancenegligibly small A cable length of 10 m is considered.
General information
Supplementary informationNote! When making the electrical connection, ensure that the sensor cable is protected against mechanical stress!
Use in the hazardous areasee instruction manuals
Category1G, 2G, 1D