Module M-LB-5112 Pepperl+Fuchs 269083
Module M-LB-5112 Pepperl+Fuchs 269083

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

M-LB-5112 269083 Pepperl+Fuchs Module

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

M-LB-5112

Part number

269083

Type

Module

Description

  • Surge protection for 2 signal lines
  • Nominal voltage 1 V DC
  • Protection module for non-grounded signal lines
  • Max. surge current (8/20 µ,s) 20 kA
  • Uninterruptable operation (auto reset)
  • Mounting on base module, pluggable
  • Up to SIL 3 acc. to IEC 61508

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications M-LB-5112 269083

The protection module limits induced transients of different causes, e. g. lightning or switching operations. The limitation is achieved by diverting the current to earth and limiting the signal circuit voltage during the duration of the overvoltage pulse. The device is HART transparent. The device is inserted onto the base module and forms the surge protection barrier together with the base module. The device can be replaced without tools by a locking lever.

Features M-LB-5112 269083

Product Description
Protection module for 2 signal lines
General specifications
Number of protected signal lines2
Topologynon-grounded
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Electrical specifications
Connectionprotected area: terminals 3, 4 unprotected area: terminals 1, 2
Rated current500 mA , restrictions see derating characteristics
Leakage current< 5 µ,A at 1 V and 25 °C (77 °F) , line-line
Nominal voltage1 V DC
Maximum continuous operating voltage6 V DC
Series resistance&le, 0.6 &Omega, per line
Impulse rating1 kV/0.5 kA (category C1) 10 kV/5 kA (category C2) 1 kA (category D1)
Impulse discharge current (10/350 µ,s)1 kA per line (2x)
Nominal discharge current (8/20 µ,s)5 kA per line (10x)
Rated surge current (8/20 µ,s)10 kA per line (1x)
Total discharge current (8/20 µ,s)20 kA (1x)
Voltage protection levelmax. 12 V line-line for nominal discharge current In max. 1400 V line-earth for nominal discharge current In
Impulse reset time< 500 ms
Insertion loss&le, 0.04 dB, at 0 ... 4 kHz, in 600 &Omega,-System &le, 3 dB, at 0 ... 450 kHz, in 100 &Omega,-System
Conformity
Degree of protectionIEC 60529:2013
Functional safetyIEC/EN 61508:2010
Surge protective devices for low voltageEN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012
Ambient conditions
Ambient temperature-40 ... 80 °C (-40 ... 176 °F) Observe the temperature range limited by derating, see section derating.
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 95 % , without condensation
Mechanical specifications
Degree of protectionIP20
Massapprox. 20 g
Dimensions6.2 x 77 x 79 mm
Mountingpluggable in base module for mounting on 35 mm DIN mounting rail
Data for application in connection with hazardous areas
CertificateBVS 17 ATEX E 070 X
Marking II 3G Ex ec IIC T6...T4 Gc
Temperature classT6 for ambient temperature &le, 60 °C T5 for ambient temperature &le, 70 °C T4 for ambient temperature &le, 80 °C
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-7:2015
International approvals
IECEx approval
IECEx certificateIECEx BVS 17.0061X
IECEx markingEx ec IIC T6...T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Designationsystem components: - base module with screw terminals M-LB-5000 - base module with spring terminals M-LB-5000.SP - place holder module M-LB-5900