Switch Amplifier KFD2-SOT3-Ex2.IO-Y1 Pepperl+Fuchs 264348
Switch Amplifier KFD2-SOT3-Ex2.IO-Y1 Pepperl+Fuchs 264348

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

KFD2-SOT3-Ex2.IO-Y1 264348 Pepperl+Fuchs Switch Amplifier

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KFD2-SOT3-Ex2.IO-Y1

Part number

264348

Type

Switch Amplifier

Description

  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Isolated passive transistor output, TTL level
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL 2 acc. to IEC 61508

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KFD2-SOT3-Ex2.IO-Y1 264348

This isolated barrier is used for intrinsic safety applications. The device transfers digital signals (NAMUR sensors or dry contacts) from a hazardous area to a safe area. Each input controls a passive transistor output. The outputs are galvanically isolated from each other. Via switches the mode of operation can be reversed and the line fault detection can be switched off. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.

Features KFD2-SOT3-Ex2.IO-Y1 264348

Product Description
24 V DC
General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 30 V DC
Ripple&le, 10 %
Rated current30 ... 20 mA
Power dissipation&le, 1.1 W including maximum power dissipation in the output
Input
Connection sidefield side
Connectionterminals 1+, 2+, 3-, 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR), see system description for electrical data
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I &le, 0.1 mA , short-circuit I &ge, 6.5 mA
Pulse/Pause ratiomin. 100 µ,s / min. 100 µ,s
Output
Connection sidecontrol side
Connectionoutput I: terminals 7, 8 , output II: terminals 10, 11
Rated voltage30 V DC
Rated current2 mA , short-circuit protected
Response time&le, 200 µ,s
Signal level1-signal: switching voltage - 0.85 V max. at 2 mA switching current 0-signal: switched off (off-state current &le, 10 µ,A)
Output Isignal , Transistor , TTL compatible
Output IIsignal , Transistor , TTL compatible
Collective error messagePower Rail
Transfer characteristics
Switching frequency&le, 5 kHz
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-2:2008
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateEXA 16 ATEX 0016 X
Marking II 3(1)G Ex nA [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
InputEx ia
Voltage10.5 V
Current17.1 mA
Power45 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approvalE106378
Control drawing116-0424 (cULus)
IECEx approval
IECEx certificateIECEx EXA 16.0009X
IECEx markingEx nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessoriespower feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03