Safety Monitor VAS-2A8L-KE4-8SE Pepperl+Fuchs 261493
Safety Monitor VAS-2A8L-KE4-8SE Pepperl+Fuchs 261493

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

VAS-2A8L-KE4-8SE 261493 Pepperl+Fuchs Safety Monitor

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

VAS-2A8L-KE4-8SE

Part number

261493

Type

Safety Monitor

Description

  • Compact safety controller up to SIL 3/PLe
  • 4 integrated, safe inputs
  • 2 integrated, safe outputs (OSSDs)
  • 8 logical, safe output groups (switchable)
  • Increased functionality through integrated expansion port
  • Parameterizable muting, timer and logic functions using SIMON+ software

Stock availability:

On request

990.4 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VAS-2A8L-KE4-8SE 261493

The AS-Interface safety monitor compact VAS-2A8L-KE4-8SE- is a control cabinet module with up to 8/4 local safe inputs and up to 8 independent outputs. The safe inputs can optionally be configured as standard inputs and signalling outputs. Two of the safe inputs are also suitable as inputs for OSSDs, the others only for potentialfree contacts. Each safe input can also be configured as two standard inputs. 8 independent AS-Interface release circuits support multiple safe AS-Interface outputs on a single address. In addition, the test pulse outputs can be switched as diagnostic outputs (not control- safe). The safe circuit for the connected consumers is created using two safety relays. The housing, which is only 22.5 mm wide, requires little space in the switch cabinet. The module is mounted by clicking it onto the 35 mm mouting rail, compliant with EN 50022. The AS-Interface and external power supply are each connected by means of a 2-station terminal block. Connection of the inputs and outputs is by means of multiple 4-station terminal blocks. This permits the simple removal of the supply during commissioning or servicing. The supply to the connected slaves is fed either internally via the module from the AS-interface or via an external supply. The current status of the inputs and outputs is indicated via yellow LEDs. Communication faults are indicated via red LEDs. The display of the operating voltage and the address 0 is provided by a green LED. A Micro-USB interface is used for configuration with the AS-i-Control Tools via ASIMON. The configuration can be transferred to a replacement device using a chip card.

Features VAS-2A8L-KE4-8SE 261493

Product Description
Safety Monitor, 8 decentralized output circuits
General specifications
AS-Interface specificationV3.0
UL File NumberE223772
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
Mission Time (TM)20 a
PFHd5.08 E-9
Indicators/operating means
LED SMStatus of safety monitor, multicolored LED green: Safety monitor OK
LED S1 ... S8Status of inputs S1 ... S8, yellow LED yellow: Contact open
LED O1, O2Status of outlputs, multicolored LED yellow: Output on
Electrical specifications
Auxiliary voltage (input)20 ... 30 VDC PELV
Insulation voltage500 V AS-Interface/UAUX:
Rated operating voltage18,0 ... 31.6 V from AS-Interface
Rated operating current&le, 200 mA from AS-Interface, &le, 4 A from AUX
Interface 1
Interface typeChip card slot
Interface 2
Interface typeMicro USB Programming interface
Input
Number/Type8 / 4 safe inputs cat. 4 or 8 standard inputs
Supply24 V UAUX
Current loading capacity10 mA per signal output 1.4 A OSSD supply output
Input currentStatic switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 &mu,s)
Output
Number/TypeOutput circuits 1 and 2 max. contact rating: 700 m ADC-13 at 24 V
Supply24 V UAUX
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005/AC:2005 EN 61000-6-4:2007/A1:2011
Machinery Directive
Directive 2006/42/ECEN 13849-1:2008/AC:2009 EN 62061:2005
Standard conformity
Electromagnetic compatibilityEN 50295:1999 EN 61000-6-2:2005/AC:2005 EN 61000-6-4:2007/A1:2011
Degree of protectionEN 60529:2000
Electrical safetyIEC 61508:2010 and EN 62061:2005 (up to SIL3) EN 13849-1:2008/AC:2009 EN 61326-3-1:2008
AS-InterfaceEN 62026-2:2013
Programming instructions
ProfileS-0.B.E
IO code0
ID codeB
ID1 codeF
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Connectionremovable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
MountingDIN mounting rail