Temperature Input LB5004A Pepperl+Fuchs 254741
Temperature Input LB5004A Pepperl+Fuchs 254741

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

LB5004A 254741 Pepperl+Fuchs Temperature Input

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

LB5004A

Part number

254741

Type

Temperature Input

Description

RTD Converter LB5004A - LB5004A

Stock availability:

On request

822.99 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications LB5004A 254741

The RTD converter accepts 2-, 3-, 4-wire RTD signals (Pt100 ... Pt1000) and slide-wire sensors from the field. Ni100 through Ni1000 can also be connected. Open and short-circuit line faults are detected. The inputs are galvanically isolated from the bus and the power supply.

Features LB5004A 254741

Slots
Occupied slots2
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Power dissipation0.35 W
Power consumption0.35 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
temperature input
Number of channels4
Suitable field devices
Field deviceresistance thermometer
Field device [3]slide-wire sensors
Field device [5]potentiometer
Field device interface
Connection2-wire sensor
Connection [2]3-wire sensor
Connection [3]4-wire sensor
Connectionchannel I: resistance/potentiometer input 1 ... 4 channel II: resistance/potentiometer input 5 ... 8 channel III: resistance/potentiometer input 9 ... 12 channel IV: resistance/potentiometer input 13 ... 16
Measurement rangePt100 (18-390 &Omega,) (500 &Omega, incl. line resistance) Pt200 (37-780 &Omega,) Pt500 (92-1952 &Omega,) Pt1000 (185-3905 &Omega,) Ni100 (69-270 &Omega,) Ni500 (345-1350 &Omega,) Ni1000 (690-2700 &Omega,)
Slide-wire sensor0 ... 10 k&Omega,
Measuring current200 µ,A
Smallest span50 &Omega, for 0.1 % accuracy
Linearity error0.1 %
Conversion timemax. 500 ms (4 channels) max. 1 s (for 4x 3-wire Pt100)
Busy after download5 ... 15 s
Lead resistancemax. 50 &Omega, per strand
Line fault detectioncan be switched on/off for each channel via configuration tool
Short-circuit< 10 &Omega,
Open-circuit> 1 k&Omega,
Transfer characteristics
Deviation
Influence of ambient temperaturemax. 0,1 %/10 K
Indicators/settings
LED indicationPower LED (P) green: supply Status LED (I) red: line fault (collective alarm) , red flashing: communication error
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-56
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz, transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g, 10 cycles frequency range 5 ... 100 Hz, transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g, 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 when mounted on backplane
Connectionremovable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 150 g
Dimensions32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
CertificatePF 08 CERT 1234 X
Marking II 3 G Ex nA [ic] IIC T4 Gc
Galvanic isolation
Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010
International approvals
IECEx approvalBVS 09.0037X
Approved forEx nA [ic] IIC T4 Gc
Marine approval
Lloyd Register15/20021
DNV GL MarineTAA0000034
Bureau Veritas Marine22449/B0 BV
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.