Gateway VBG-PB-K20-DMD-EV Pepperl+Fuchs 254524
Gateway VBG-PB-K20-DMD-EV Pepperl+Fuchs 254524

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

VBG-PB-K20-DMD-EV 254524 Pepperl+Fuchs Gateway

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

VBG-PB-K20-DMD-EV

Part number

254524

Type

Gateway

Description

AS-Interface gateway VBG-PB-K20-DMD-EV

Stock availability:

On request

1520.14 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VBG-PB-K20-DMD-EV 254524

The VBG-PB-K20-DMD-EV is a PROFIBUS gateway with a double master according to AS-Interface specification 3.0. The design of the K20 in stainless steel with IP20 is particularly suited for use in switching cabinets for snap on mounting on the 35 mm mounting rail. The gateway in accordance with the AS-Interface specification V 3.0 is used to connect AS-Interface systems to a higher-level net. It acts as a master for the AS-Interface segment and as a slave for the higher-level net. During cyclic data exchange, the digital data of an AS-Interface segment is transferred. Analog values as well as the complete command set of the new AS-Interface specification are transferred using a command interface. The address allocation and acceptance of the target configuration can be achieved via the keys. 7 LEDs fitted to the front panel indicate the actual state of the AS-Interface branch. With the graphical display, the commissioning of the AS-Interface circuits and testing of the connected peripherals can take place completely separately from the commissioning of the higher-level network and the programming. With the 4 switches, all functions can be controlled and visualized on the display. An RJ-45 Ethernet port provides a way of exporting data relating to the gateway, network and operation directly from the gateway for extended local diagnosis purposes. Via the RJ-45 Ethernet diagnostic interface, up to 31 devices can establish a secure cross-communication. The device has a card slot for a memory card for the storage of configuration data. The integrated data decoupling allows to operate 2 AS-Interface circuits with just a standard power supply. The redundant power supply guarantees that the double master remains in function and is diagnosticable, when a failure of a power supply unit in one of the two AS-interfaces circles occures. Also communication with the superior field bus is not disturbed by the failure of a power supply. PLC Functionality Optionally the gateway is also available with PLC functionality. Therefor you can order a code key VAZ-CTR additionally.

Features VBG-PB-K20-DMD-EV 254524

Product Description
PROFIBUS Power Hub gateway with data decoupling, double master for 2 AS-Interface networks
General specifications
AS-Interface specificationV3.0
PLC-Functionalityactivateable
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
Data decouplingintegrated
UL File NumberE223772
Indicators/operating means
DisplayIlluminated graphical LC display for addressing and error messages
LED PROFIBUSPROFIBUS master detected, LED green
LED AS-i ACTIVEAS-Interface operation normal, LED green
LED CONFIG ERRconfiguration error, LED red
LED PRG ENABLEautom. programming, LED green
LED POWERvoltage ON, LED green
LED PRJ MODEprojecting mode active, LED yellow
LED U AS-iAS-Interface voltage, LED green
Button4
Switch SETSelection and setting of a slave address
OK buttonMode selection traditional-graphical/confirmation
Button MODEMode selection PRJ-operation/save configuration/cursor
ESC buttonMode selection traditional-graphical/cancel
Electrical specifications
Insulation voltage&ge, 500 V
Rated operating voltagefrom AS-Interface
Rated operating currentapprox. 250 mA PELV
Interface 1
Interface typeRS-485
ProtocolPROFIBUS in accordance with IEC 61158/IEC 61784-1
Transfer rate9.6 kBit/s / 12 MBit/s , Automatic baud rate detection
Interface 2
Interface typeRJ-45 Ethernet Programming and diagnostics interface
Interface 3
Interface typeChip card slot
Connection
PROFIBUSSub-D interface
EthernetRJ-45
AS-Interfacespring terminals, removable
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Shock resistanceEN 61131-2:2004
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Material
HousingStainless steel
Mass460 g
Construction typeLow profile housing