Digital input LB1109A Pepperl+Fuchs 223078
Digital input LB1109A Pepperl+Fuchs 223078

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

LB1109A 223078 Pepperl+Fuchs Digital input

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

LB1109A

Part number

223078

Type

Digital input

Description

Digital Input LB1109A

Stock availability:

On request

581.01 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications LB1109A 223078

The device accepts digital input signals of NAMUR sensors or mechanical contacts from the hazardous area. Open and short circuit line faults are detected. The inputs are galvanically isolated from the bus and the power supply.

Features LB1109A 223078

Slots
Occupied slots1
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies LB9***
Power dissipation1.55 W
Power consumption1.55 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Digital input
Number of channels8
Sensor interface
ConnectionNAMUR sensor
Connection [2]volt-free contact
ConnectionTerminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-, 9+, 10-, 11+, 12-, 13+,14-, 15+, 16-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Switching point/switching hysteresis1.2 ... 2.1 mA / ± 0.2 mA
Voltage8.2 V
Internal resistor1 k&Omega,
Line fault detectioncan be switched on/off for each channel via configuration tool
Connectionmechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring
Short-circuit< 360 &Omega,
Open-circuit< 0.35 mA
Minimum pulse duration15 ms
Indicators/settings
LED indicationPower LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-8) red: line fault (lead breakage or short circuit) , yellow: signal (per channel)
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-56
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz, transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g, 10 cycles frequency range 5 ... 100 Hz, transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g, 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 when mounted on backplane
Connectionremovable front connector with spring terminal (0.14 ... 0.5 mm2)
Massapprox. 90 g
Dimensions16 x 100 x 102 mm (0.63 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
EU-type examination certificateEXA 13 ATEX 0036X
Marking II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC
Input
Voltage10 V
Current13 mA
Power33 mW (linear characteristic)
Galvanic isolation
Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2011 EN 60079-11:2011 EN 60079-15:2010
International approvals
ATEX approvalEXA 13 ATEX 0036X
UL approvalE106378
IECEx approvalEXA 13.0003X
Approved forEx nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
Marine approval
Lloyd Register15/20021
Bureau Veritas Marine22449/B0 BV
General information
System informationThe module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.