Solenoid Driver KFD2-SL2-Ex1.LK.1045 Pepperl+Fuchs 203284
Solenoid Driver KFD2-SL2-Ex1.LK.1045 Pepperl+Fuchs 203284

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

KFD2-SL2-Ex1.LK.1045 203284 Pepperl+Fuchs Solenoid Driver

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KFD2-SL2-Ex1.LK.1045

Part number

203284

Type

Solenoid Driver

Description

Solenoid Driver KFD2-SL2-Ex1.LK.1045

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KFD2-SL2-Ex1.LK.1045 203284

This isolated barrier is used for intrinsic safety applications. It supplies power to solenoids, LEDs, and audible alarms, located in a hazardous area. It is controlled via a logic signal. The input has two defined states: 1- Signal = 16 V DC ... 30 V DC, 0- Signal = 0 V DC ... 5 V DC. The current consumption of the input is about 3 mA. At full load, 10 V at 45 mA is available for the hazardous area application. If the field impedance is > 10 kΩ for lead breakage or < 50 Ω for short circuits a line fault is detected. During an error condition, the fault indication output de-energizes. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output.

Features KFD2-SL2-Ex1.LK.1045 203284

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 30 V DC
Power dissipationmax. 1.5 W
Power consumptionmax. 2 W at 45 mA output current
Input
Connection sidecontrol side
Connectionterminals 7, 8
Input currentapprox. 3 mA
Signal level1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC
Output
Connection sidefield side
Output I
Connectionterminals 1+, 2- or 3-
Internal resistor300 &Omega,
Currentmax. 45 mA
Voltagemin. 10 V
Open loop voltagemin. 23.5 V
Output signalThese values are valid for the rated operating voltage 19 ... 30 V DC.
Energized/De-energized delay&le, 20 ms / &le, 20 ms
Line fault detectionsignal at short-circuit RB <50 &Omega,, lead breakage RB> 10 k&Omega, , test current < 650 µ,A
Output IIfault signal
Connectionterminals 10, 11, 12 , non-intrinsically safe
Contact loading253 V AC/2 A/cos &phi, > 0.7, 40 V DC/2 A resistive load
Mechanical life2 x 107 switching cycles
Energized/De-energized delay&le, 20 ms / &le, 20 ms
Galvanic isolation
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output I, II against eachotherreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output II/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateZELM 99 ATEX 0015
Marking II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Output IEx ia
Voltage26 V
Current93 mA
Power607 mW (linear characteristic)
Supply
Maximum safe voltage40 V (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Collective error message
Maximum safe voltage40 V (Attention! The rated voltage can be lower.)
CertificateTÜV 02 ATEX 1820 X
Marking II 3G Ex nA nC IIC T4 Gc
Output II
Contact loading50 V AC/2 A/cos &phi, > 0.7, 40 V DC/2 A resistive load
Galvanic isolation
Output I/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000
International approvals
CSA approval
Control drawing116-0362
IECEx approval
IECEx certificateIECEx ZLM 14.0001
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-BU(-UPR-03)