HiD2026 196449 Pepperl+Fuchs Transmitter Power Supply

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

HiD2026

Part number

196449

Type

Transmitter Power Supply

Description

  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • 2-wire SMART transmitter
  • Output for 4 mA ... 20 mA or 1 V ... 5 V
  • Low power dissipation
  • Up to SIL 2 acc. to IEC 61508

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications HiD2026 196449

This isolated barrier is used for intrinsic safety applications. It provides 2-wire SMART transmitters with power in the hazardous area, and repeats the current to drive a safe area load. Bi-directional communication is supported for SMART transmitters that use current modulation to transmit data and voltage modulation to receive data. The outputs are isolated from the inputs and are referenced to the power supply common. This module mounts on a HiD Termination Board.

Features HiD2026 196449

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-), 2a(+), 2b(+)
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Rated current95 mA at 24 V, 20 mA output
Power dissipation0.8 W at 24 V (per channel)
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-), 1a(+), 1b(-)
Input current4 ... 20 mA , current limit 26 mA typ.
Ripple10 mV eff
Voltagemin. 15.5 V at 20 mA
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-), 10a(+), 9a(-)
Load0 ... 650 &Omega,
Output signal4 ... 20 mA or 1 ... 5 V (on 250 &Omega,, 0.1 % internal shunt)
Ripple10 mV eff on a load of 250 &Omega,
Response time40 ms , 10 ... 90 % step change
Transfer characteristics
Calibrated accuracy< ± 0.1 % of full-scale value (current output)
Influence of temperature< 2 µ,A/K (0 ... 60 °C (32 ... 140 °F)), < 4 µ,A/K (-20 ... 0 °C (-4 ... 32 °F)) 0.01 %/ K
Frequency rangecommunication channel: 0.5 ... 40 kHz within 3 db, (-6 db at 100 kHz), Tx to output and output to Tx, suitable for use with SMART transmitters using HART or similar protocol
Influence of load< ± 0.1 % of full-scale value from 0 ... 650 &Omega,
Linearity< ± 0.1 % of full-scale value
Galvanic isolation
Input/inputsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 60 V
Indicators/settings
Display elementsLED
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006 For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 106 x 128 mm (0.7 x 4.2 x 5 inch)
Mountingon Termination Board
Data for application in connection with hazardous areas
EU-Type Examination CertificateCESI 10 ATEX 025
Marking II (1)GD [Ex ia] IIC, [Ex iaD] [circuit(s) in zone 0/1/2/20/21/22]
CertificatePF 10 CERT 1609 X
Marking II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing366-005CS-12B (cCSAus)
IECEx approvalIECEx CES 10.0011