Inductive sensor NCB15+U4+N0-V1 Pepperl+Fuchs 184674
Inductive sensor NCB15+U4+N0-V1 Pepperl+Fuchs 184674

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

NCB15+U4+N0-V1 184674 Pepperl+Fuchs Inductive sensor

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

NCB15+U4+N0-V1

Part number

184674

Type

Inductive sensor

Description

Inductive sensor NCB15+U4+N0-V1

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications NCB15+U4+N0-V1 184674

If you are inspecting Pepperl+Fuchs NCB15+U4+N0-V1 184674, get in touch with FAMAGA, the world's main producer of industrial equipment. Our company has progressed for more than ten years - these are years of experience, which are illustrated in the quality of outcomes and individual attention to each client. We praise everyone, who conspired with us - thus, our regular customers obtain the most flexible purchase terms and discounts on the manufacturing equipment market. At this moment, there are more than 4 thousand such clients, and we constantly make new agreements. More than 700 purchases are terminated per day, because FAMAGA delivers all over the planet . A advanced logistics system and a partnership network guide us to conduct our goods anywhere in the planet promptly without disreputing product quality.

A specific source of good name for FAMAGA is its team members, each of whom contributes to common cause. We propose into our team only professionals, who already have experience in the range of machine made streamlined equipment.

All products from FAMAGA are guaranteed - we are responsible for the outcome of our work. Nowadays, more than 10 million units of products have been supplied, and this quantity is ascending every day. We are happy that purchasers choose FAMAGA again and again, and we are happy to make more exceptional and technologically advanced industrial equipment so as stay in control.

To consult or place an order, contact us or send a message to the online chat on our site. You can also dispatch a list of the necessary equipment to the email of our company - we will contact you ourselves with a prepared commercial proposal from FAMAGA.

Features NCB15+U4+N0-V1 184674

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance15 mm
Installationflush
Assured operating distance0 ... 12.15 mm
Actual operating distance13.5 ... 16.5 mm typ.
Reduction factor rAl 0.28
Reduction factor rCu 0.25
Reduction factor r304 0.75
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Switching frequency0 ... 400 Hz
Hysteresis1 ... 15 typ. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected&le, 1 mA
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd5128 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
FM approval
Control drawing116-0165
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0451
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection typeConnector plug M12 x 1 , 4-pin
Housing materialPBT/metal
Sensing facePBT
Degree of protectionIP68
Equipment protection level Ga
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB15+U...+N0...
Effective internal capacitancemax. 110 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 160 µ,H , a cable length of 10 m is considered.
Ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB15+U...+N0...
Effective internal capacitancemax. 110 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 160 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB15+U...+N0...
Effective internal capacitancemax. 110 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 160 µ,H , a cable length of 10 m is considered.
General information
Use in the hazardous areasee instruction manuals
Category1G, 2G, 1D