Inductive sensor NCB50-FP-A2-P1-3G-3D Pepperl+Fuchs 129866
Inductive sensor NCB50-FP-A2-P1-3G-3D Pepperl+Fuchs 129866

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

NCB50-FP-A2-P1-3G-3D 129866 Pepperl+Fuchs Inductive sensor

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

NCB50-FP-A2-P1-3G-3D

Part number

129866

Type

Inductive sensor

Description

Inductive sensor NCB50-FP-A2-P1-3G-3D

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications NCB50-FP-A2-P1-3G-3D 129866

If you are questing Pepperl+Fuchs NCB50-FP-A2-P1-3G-3D 129866, connect FAMAGA, the world's foremost provider of factory-made equipment. Our company has lasted for more than ten years - these are years of experience, which are depicted in the quality of merchandises and private attention to each consumer. We appreciate everyone, who collaborated with us - therefore, our regular customers get the most helpful purchase terms and discounts on the manufacturing equipment market. At this time, there are more than 4000 such consumers, and we constantly arrange new agreements. More than 650 purchases are terminated per day, because FAMAGA operates all over the world . A well-built logistics bond and a partnership network guide us to deliver our units anywhere in the world on-time without damaging product quality.

A specific source of pride for FAMAGA is its employees, each of whom contributes to our work. We request into our team only experts, who already have experience in the field of machine made streamlined equipment.

All outcomes from FAMAGA are guaranteed - we are responsible for the cause of our work. At this moment, more than 10 million units of products have been shipped, and this quantity is growing every day. We are proud that consumers choose FAMAGA again and again, and we are glad to make more advanced and technologically advanced industrial equipment so as not to lower the bar.

To consult or book, get in touch with us or send a message to the online chat on our site. You can also send a list of the required equipment to the email of corporation - we will contact you ourselves with a made commercial proposal from FAMAGA.

Features NCB50-FP-A2-P1-3G-3D 129866

General specifications
Switching functioncomplementary
Output typePNP
Rated operating distance50 mm
Installationflush
Output polarityDC
Assured operating distance0 ... 40.5 mm
Reduction factor rAl 0.38
Reduction factor rCu 0.35
Reduction factor r304 0.83
Output type4-wire
Nominal ratings
Operating voltage10 ... 60 V DC
Switching frequency0 ... 80 Hz
Hysteresistyp. 3 %
Reverse polarity protectionreverse polarity protected
Voltage drop&le, 3 V
Operating current0 ... 200 mA
Off-state current0 ... 0.5 mA
No-load supply current&le, 20 mA
Time delay before availability&le, 300 ms
Operating voltage indicatorLED, green
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd670 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
StandardsEN 60947-5-2:2007 IEC 60947-5-2:2007
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCertified by China Compulsory Certification (CCC)
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection typescrew terminals
Information for connectionA maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 %
Core cross-sectionup to 2.5 mm2
Minimum core cross-sectionwithout wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2
Maximum core cross-sectionwithout wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2
Housing materialPBT
Sensing facePBT
Housing basePBT
Degree of protectionIP67
Equipment protection level Gc (nA)
CertificatePF 15CERT3754 X
CE marking[*PD-Z02586A*]
ATEX marking II 3G Ex nA IIC T6 Gc The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-15:2010 Ignition protection category n Use is restricted to the following stated conditions
Special conditions
Maximum operating current ILThe maximum permissible load current must be restricted to the values given in the following list. High load currents and load short-circuits are not permitted.
Maximum operating voltage UBmaxThe maximum permissible operating voltage UB max is restricted to the values in the following list. Tolerances are not permissible.
Maximum permissible ambient temperature TUmaxdependant of the load current IL and the max. operating voltage UBmax Information can be taken from the following list.
at UBmax=60 V, IL=200 mA44 °C (111.2 °F)
at UBmax=60 V, IL=100 mA45 °C (113 °F)
at UBmax=60 V, IL=25 mA47 °C (116.6 °F)
at UBmax=30 V, IL=200 mA50 °C (122 °F)
at UBmax=30 V, IL=100 mA53 °C (127.4 °F)
at UBmax=30 V, IL=50 mA56 °C (132.8 °F)
Equipment protection level Dc
CE marking[*PD-Z02586A*]
ATEX marking II 3D IP67 T 95 °C (203 °F) X
StandardsEN 50281-1-1 Protection via housing Use is restricted to the following stated conditions
Special conditions
Maximum heating (Temperature rise)dependant of the load current IL and the max. operating voltage UBmax Information can be taken from the following list. The maximum surface temperature at maximum ambient temperature is given in the Ex identification of the apparatus.
at UBmax=60 V, IL=200 mA25 K
at UBmax=60 V, IL=100 mA24 K
at UBmax=60 V, IL=25 mA22 K
at UBmax=30 V, IL=200 mA19 K
at UBmax=30 V, IL=100 mA16 K
at UBmax=30 V, IL=50 mA14 K
Equipment protection level Dc (tc)
CE marking[*PD-Z02586A*]
ATEX marking II 3D Ex tc IIIC T80°C Dc The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-31:2014 Protection by enclosure tc Some of the information in this instruction manual is more specific than the information provided in the datasheet.
GeneralThe corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet.
Special conditions
Maximum permissible ambient temperature TUmaxdependant of the load current IL and the max. operating voltage UBmax Information can be taken from the following list.
at UBmax=60 V, IL=200 mA44 °C (111.2 °F)
at UBmax=60 V, IL=100 mA45 °C (113 °F)
at UBmax=60 V, IL=25 mA47 °C (116.6 °F)
at UBmax=30 V, IL=200 mA50 °C (122 °F)
at UBmax=30 V, IL=100 mA53 °C (127.4 °F)
at UBmax=30 V, IL=50 mA56 °C (132.8 °F)
General information
Use in the hazardous areasee instruction manuals
Category3G, 3D