Inductive sensor NJ30+U1+N Pepperl+Fuchs 106685
Inductive sensor NJ30+U1+N Pepperl+Fuchs 106685

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

NJ30+U1+N 106685 Pepperl+Fuchs Inductive sensor

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

NJ30+U1+N

Part number

106685

Type

Inductive sensor

Description

Inductive sensor NJ30+U1+N

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications NJ30+U1+N 106685

If you are inspecting Pepperl+Fuchs NJ30+U1+N 106685, catch up with FAMAGA, the world's key supplier of industrial equipment. Our company has lasted for more than ten years - these are years of experience, which are expressed in the quality of goods and individual attention to each consumer. We esteem everyone, who worked with us - thus, our regular clients obtain the most beneficial purchase conditions and discounts on the machine made streamlined equipment market. Today, there are more than 4 thousand such purchasers, and we constantly sign new agreements. More than 700 affairs are settled per day, because FAMAGA works all over the planet . A well-elaborated logistics system and a partnership network guide us to conduct our elements anywhere in the world on-time without undermining product quality.

A particular source of repute for FAMAGA is its staff members, each of whom contributes to our work. We propose into our team only experts, who already have experience in the sphere of industrial equipment.

All products from FAMAGA are ensured - we are responsible for the result of our work. Now, more than 10 million units of products have been shipped, and this bulk is increasing every day. We are happy that users choose FAMAGA again and again, and we are eager to make more exceptional and technologically modern industrial equipment so as to stay on the top.

To request or place an order, contact us or send a message to the online chat on our site. You can also direct a list of the required equipment to the email of corporation - we will contact you ourselves with a prepared commercial proposal from FAMAGA.

Features NJ30+U1+N 106685

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance30 mm
Installationnon-flush
Assured operating distance0 ... 24.3 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8 V
Switching frequency0 ... 150 Hz
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected&le, 1 mA
Functional safety related parameters
MTTFd3630 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
FM approval
Control drawing116-0165
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0451
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typescrew terminals
Information for connectionA maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 %
Core cross-sectionup to 2.5 mm2
Minimum core cross-sectionwithout wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2
Maximum core cross-sectionwithout wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2
Housing materialPBT
Sensing facePBT
Degree of protectionIP68
NoteTightening torque: 1.8 Nm (housing)
Equipment protection level Ga
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 30+U.+N...
Effective internal capacitancemax. 160 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 130 µ,H , a cable length of 10 m is considered.
Ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 30+U.+N...
Effective internal capacitancemax. 160 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 130 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 30+U.+N...
Effective internal capacitancemax. 160 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 130 µ,H , a cable length of 10 m is considered.
General information
Use in the hazardous areasee instruction manuals
Category1G, 2G, 1D