Inductive sensor NJ6-22-N-G-5M Pepperl+Fuchs 106461
Inductive sensor NJ6-22-N-G-5M Pepperl+Fuchs 106461

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

NJ6-22-N-G-5M 106461 Pepperl+Fuchs Inductive sensor

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

NJ6-22-N-G-5M

Part number

106461

Type

Inductive sensor

Description

Inductive sensor NJ6-22-N-G-5M

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications NJ6-22-N-G-5M 106461

If you are inspecting Pepperl+Fuchs NJ6-22-N-G-5M 106461, reach FAMAGA, the world's prime producer of streamlined equipment. Our company has operated for more than ten years - these are cycles of experience, which are expressed in the quality of goods and individual attention to each orderer. We admire everyone, who conspired with us - thus, our regular clients pick up the most acceptable purchase terms and discounts on the machine made streamlined equipment market. Today, there are more than 4500 such clients, and we constantly compose new agreements. More than 700 affairs are settled per day, because FAMAGA supplies all over the earth . A advanced logistics bond and a partnership network guide us to conduct our goods anywhere in the world promptly without undermining product quality.

A particular source of good name for FAMAGA is its workers, each of whom contributes to our work. We propose into our team only experts, who already have experience in the direction of industrial equipment.

All goods from FAMAGA are ensured - we are responsible for the aftereffect of our work. At this moment, more than 10 million units of products have been shipped, and this bulk is increasing every day. We are glad that clients choose FAMAGA again and again, and we are pleased to make more exceptional and technologically developed industrial equipment so as keep on top of it.

To inquire or place an order, contact us or send a message to the online chat on our site. You can also forward a list of the required equipment to the email of corporation - we will contact you ourselves with a ready-made commercial proposal from FAMAGA.

Features NJ6-22-N-G-5M 106461

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance6 mm
Installationflush
Assured operating distance0 ... 4.86 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8 V
Switching frequency0 ... 2000 Hz
Hysteresistyp. %
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected&le, 1 mA
Functional safety related parameters
MTTFd4566 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007 IEC 60947-5-2:2007
Approvals and certificates
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typecable PVC , 5 m
Core cross-section0.75 mm2
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP68
Cable
Bending radius> 10 x cable diameter
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 2G Ex ia IIC T6&hellip,T1 Gb The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 6-22-N...
Effective internal capacitancemax. 130 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 100 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Equipment protection level Gc (ic)
CertificatePF 13 CERT 2895 X
CE marking[*PD-Z02586A*]
ATEX marking II 3G Ex ic IIC T6&hellip,T1 Gc The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection category ic Use is restricted to the following stated conditions
Effective internal capacitancemax. 130 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 100 µ,H , A cable length of 10 m is considered.
Special conditions
for Pi=34 mW, Ii=25 mA, T655 °C (131 °F)
for Pi=34 mW, Ii=25 mA, T555 °C (131 °F)
for Pi=34 mW, Ii=25 mA, T4-T155 °C (131 °F)
for Pi=64 mW, Ii=25 mA, T655 °C (131 °F)
for Pi=64 mW, Ii=25 mA, T555 °C (131 °F)
for Pi=64 mW, Ii=25 mA, T4-T155 °C (131 °F)
for Pi=169 mW, Ii=52 mA, T641 °C (105.8 °F)
for Pi=169 mW, Ii=52 mA, T541 °C (105.8 °F)
for Pi=169 mW, Ii=52 mA, T4-T141 °C (105.8 °F)
for Pi=242 mW, Ii=76 mA, T629 °C (84.2 °F)
for Pi=242 mW, Ii=76 mA, T529 °C (84.2 °F)
for Pi=242 mW, Ii=76 mA, T4-T129 °C (84.2 °F)
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 6-22-N...
Effective internal capacitancemax. 130 µ,F A cable length of 10 m is considered.
Effective internal inductancemax. 100 µ,H A cable length of 10 m is considered.
Equipment protection level Dc (tc)
CE marking[*PD-Z02586A*]
ATEX marking II 3D Ex tc IIIC T80°C Dc The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-31:2014 Protection by enclosure tc Some of the information in this instruction manual is more specific than the information provided in the datasheet.
GeneralThe corresponding datasheets, declarations of conformity, EU type examination certificates, certificates, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents are available at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet.
Special conditions
Maximum permissible ambient temperature TUmaxValues can be obtained from the following list, depending on the max. operating voltage Ub max and the minimum series resistance Rv.
at UBmax=9 V, RV=562 &Omega,58 °C (136.4 °F)
using an amplifier in accordance with EN 60947-5-658 °C (136.4 °F)
General information
Use in the hazardous areasee instruction manuals
Category2G, 3G, 3D