Fieldbus KLD2-PR-1.IEC Pepperl+Fuchs 099345
Fieldbus KLD2-PR-1.IEC Pepperl+Fuchs 099345

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

KLD2-PR-1.IEC 099345 Pepperl+Fuchs Fieldbus

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KLD2-PR-1.IEC

Part number

099345

Type

Fieldbus

Description

  • Output: 24 ... 26 V/400 mA
  • For extension of fieldbus segments
  • High-power trunk for high device count and long cable lengths
  • Installation in Zone 2/Class I, Div. 2
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Fixed, high-availability terminator
  • High efficiency, low heat dissipation
  • Supply via Power Rail

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KLD2-PR-1.IEC 099345

The fieldbus power repeater is an all-in-one module with galvanic isolation for extending single fieldbus segments. It repeats the fieldbus signal thereby restoring waveform and signal level. The two segments interconnected are considered separate physical layers for extension of cable distance and device count. Power output is designed for long cable lengths and device counts suiting the needs of most fieldbus applications. Device couplers provide explosion protection for live work at the spur where needed. Availability and a long service life are achieved through a passive impedance filter and an optimized design for low heat dissipation. Modules can be mounted with no spacing required in any direction for an optimized and space-saving cabinet layout.

Features KLD2-PR-1.IEC 099345

General specifications
Design / MountingCabinet installation
Supply
ConnectionPower Rail or terminals 47+, 48-
Rated voltage20 ... 35 V DC
Ripple&le, 10 %
Rated current380 mA ... 760 mA
Fieldbus interface
Field-side
Connectionterminals 3, 15+, 2, 14-
Rated voltage24 ... 26 V DC
Rated currentmax. 400 mA
Terminating impedance100 &Omega, , integrated
Host-side
ConnectionPower Rail or terminals 28, 40+, 29, 41-
Rated voltage9 ... 32 V DC (supplied switch S2 in pos. I) 0 V DC (not supplied switch S2 in pos. II)
Terminating impedance100 &Omega, switchable off and on via rotary switch S1: 1 -> on, 0 -> off
Galvanic isolation
Field-side/Host-sidefunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Host-side/Supplyfunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Field-side/Supplyfunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
All circuits/FEfunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
All circuits/screenfunctional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Galvanic isolationEN 50178
Electromagnetic compatibilityNAMUR NE 21
Degree of protectionIEC/EN 60529
Fieldbus standardIEC 61158-2, ISA S 50.02 part 2
Climatic conditionsDIN IEC 721
Ambient conditions
Classification3K3
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-20 ... 85 °C (-4 ... 185 °F)
Relative humidity< 75 %
Pollution degreemax. 2, according to IEC 60664
Mechanical specifications
Connection typeTerminals
Core cross-sectionup to 2.5 mm2
Housing80 mm x 115 mm x 107 mm
Degree of protectionIP20
Massapprox. 600 g
MountingDIN rail mounting
Data for application in connection with hazardous areas
Statement of conformityTÜV 01 ATEX 1788X
Group, category, type of protection, temperature class 3G EEx nA II T4
Directive conformity
Directive 94/9/ECEN 50021:1999
International approvals
FM approvalCoC 3015900
Approved forClass I, Division 2, Groups A, B, C, D