Trip amplifier 8R 01 Pepperl+Fuchs 049410
Trip amplifier 8R 01 Pepperl+Fuchs 049410

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

8R 01 049410 Pepperl+Fuchs Trip amplifier

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

8R 01

Part number

049410

Type

Trip amplifier

Description

  • 8-channel
  • Contact or logic control input
  • 1 relay output per channel with 2 NO contacts each
  • Output relay LED-status indication

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications 8R 01 049410

This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device can be used in conjunction with fault signaling systems, for controlling switching circuits, for the transmission of switch commands, and for the galvanic isolation of two circuits. The relays can be driven with 24 V DC or by means of an input logic. The device has one relay output per channel with two NO contacts each.

Features 8R 01 049410

General specifications
Signal typeDigital Output
Input
Connectionchannel 1: z2, z4 channel 2: z6, z8 channel 3: z10, z12 channel 4: z14, z16 channel 5: z18, z20 channel 6: z22, z24 channel 7: z26, z28 channel 8: z30, z32
Input current&le, 15 mA
Signal level1-signal: 20.4 ... 27.6 V DC 0-signal: 0 ... 1.9 V DC
Output
Connectionchannel 1: b2, b4, d2, d4 channel 2: b6, b8, d6, d8 channel 3: b10, b12, d10, d12 channel 4: b14, b16, d14, d16 channel 5: b18, b20, d18, d20 channel 6: b22, b24, d22, d24 channel 7: b26, b28, d26, d28 channel 8: b30, b32, d30, d32
Outputsignal , relay relay output with 2 NO contacts each (per channel)
Contact loading50 V AC/4 A/200 VA (cos &phi, > 0.7), 40 V DC/4 A/160 W resistive load
Energized/De-energized delay&le, 10 ms (typical 5 ms)/&le, 6 ms (typical 3 ms)
Mechanical life5 x 107 switching cycles
Bounce time1 ms
Transfer characteristics
Switching frequency10 Hz
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECThe device has been used for the same applications for several years. It therefore features an appropriate electromagnetic field immunity. The device must not be used in new plants.
Conformity
Insulation coordinationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connection48-pin plug connector acc. to DIN 41612 , series 2 , type F , z, b and d provided
Massapprox. 200 g
Dimensions20 x 128 x 193 mm (0.8 x 5 x 7.5 inch)