Module VAA-4E4A-KE5-ZEJQ/R Pepperl+Fuchs 269780
Module VAA-4E4A-KE5-ZEJQ/R Pepperl+Fuchs 269780

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

VAA-4E4A-KE5-ZEJQ/R 269780 Pepperl+Fuchs Module

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

VAA-4E4A-KE5-ZEJQ/R

Part number

269780

Type

Module

Description

AS-Interface sensor/actuator module VAA-4E4A-KE5-ZEJQ/R

Stock availability:

On request

185.8 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VAA-4E4A-KE5-ZEJQ/R 269780

The AS-Interface connecting module VAA-4E4A-KE5-ZEJQ/R-KRO is a switch cabinet module with 4 inputs and 4 relay contact outputs. The housing is only 19 mm wide and takes up little space in the switch cabinet. The module is mounted by snapping onto the 35 mm DIN rail in compliance with EN 50022. The connection is made via removable 4-pin push-in terminal blocks. For AS-i+ and AS-i-, two connections are available in each case, these connections are bridged in the terminal block. In case of i-, terminals 5 and 6 as well as 7 and 8 are bridged in the terminal block. If the terminal block is disconnected from the module, the link between these connections is retained. The terminal blocks are mechanically coded. The supply to the inputs and the connected sensors can be fed either from the internal supply of the module from the AS-Interface or via an external UEXT voltage source. A switch located on the side of the module changes the source. The internal input supply is displayed via the INT LED. The relevant IN and OUT LEDs display the current switching status of the inputs and outputs. Notes: The device is equipped with a communication monitor, which deactivates the outputs if the AS-Interface does not communicate with the module for more than 40 ms. The communication monitor can be deactivated via the parameter P0. Filters that suppress pulses with a duration of 2 ms or less at the inputs can be connected via the parameter P1. Parameter P2 activates the AS-Interface synchronous mode. Installation, Commissioning, and Maintenance: Install the device in a closed electrical plant where only electricians or persons with appropriate electrical training have access. The relevant laws, guidelines, and standards that apply for the application or intended use must be observed. The device must be installed in a switch cabinet or switch box that meets degree of protection IP54 as a minimum. Additional requirements for the AS-Interface power supply: If voltages that are not in accordance with PELV/SELV are connected to the relay contact outputs, then it must be ensured that the AS-Interface supply voltage does not exceed 36 V, even in the event of a fault. Daisy-Chaining Devices: Insulation to the outer surfaces of the housing: Basic insulation in accordance with EN 60664-1. To provide reliable and double insulation, devices in the direct vicinity must have basic insulation as a minimum.

Features VAA-4E4A-KE5-ZEJQ/R 269780

Product Description
Cabinet module 4 inputs and 4 relay outputs
General specifications
Slave typeStandard slave
AS-Interface specificationV3.0
Required master specification&ge, V2.0
UL File NumberE223772
MTBF224 a
Indicators/operating means
LED FAULTFault display, Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply
LED INTInternal input supply active, LED green
LED PWRAS-Interface voltage, green LED green: voltage OK flashing green: address 0
LED INswitching state (input), 4 LED yellow
LED OUTSwitching state (output), 4 LED yellow
Electrical specifications
Auxiliary voltage (input)12 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current&le, 35 mA (without sensors) / max. 230 mA
Surge protectionO1 ... O4: Over voltage category II UEXT, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 3-wire sensors (PNP), DC
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage21 ... 31 V DC (INT)
Current loading capacity&le, 150 mA, overload- and short-circuit protected (INT)
Input current&le, 5.6 mA (max.)
Switching pointaccording to DIN EN 61131-2 (type 1)
0 (unattenuated)&le, 0.5 mA
1 (attenuated)&ge, 2 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type4 relay outputs, normally open
Supplynone
Nominal load
Per contact2 A/30 VDC, 2 A/250 VAC For more information, see the Galvanic Isolation section
Per module8 A
Control circuit&le, 11 mA per relay (from AS-Interface)
Switching delay< 10 ms (AS-Interface/contact)
Usage categoryDC-13 and AC-14
Switching
Mechanical5 x 107
Electrical2 x 105 (250 VAC, 2 A, cos &phi, = 0.4)
Galvanic isolation
Input/Outputsafe isolation, Rated insulation voltage 252 Veff
Input/AS-InterfaceSwitch position INT: None Switch setting EXT: safe isolation, rated insulation voltage 92 Veff
Output/OutputBasic insulation, rated insulation voltage 250 Veff, in phase
Output/AS-Interfacesafe isolation, Rated insulation voltage 252 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Low voltage
Directive 2006/95/ECEN 60664-1:2007
Standard conformity
Galvanic isolationEN 60664-1:2007
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Electrical safetyIEC 61140:2009
InputEN 61131-2:2004
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013
Programming instructions
ProfileS-7.0
IO code7
ID code0
ID1 codeF
ID2 codeE
Data bits (function via AS-Interface) input output
D0 IN1 O1
D1 IN2 O2
D2 IN3 O3
D3 IN4 O4
Parameter bits (programmable via AS-i)function
P0Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
P1Input filter P1 = 0 input filter on, pulse suppression &le, 2 ms P1 = 1 input filter off (default settings)
P2Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings)
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude&le, 2000 m above MSL
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree2
Mechanical specifications
Degree of protectionIP20 Installation in an enclosure with a minimum protection class of IP54 required
ConnectionRemovable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass125 g
MountingDIN mounting rail