We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.
Manufacturer
Pepperl+Fuchs
Country
Germany
Part number
306132
Type
Inductive sensor
Description
Inductive sensor NJ5-11-N-G-5M
Stock availability:
On request
If you are inspecting Pepperl+Fuchs 306132, make contact with FAMAGA, the world's main provider of mechanized equipment. Our company has functioned for more than ten years - these are cycles of experience, which are represented in the quality of outcomes and individual attention to each purchaser. We praise everyone, who joined with us - so, our regular clients procure the most desirable purchase conditions and discounts on the factory-made equipment market. At this moment, there are more than 4500 such customers, and we constantly sign new agreements. More than 600 transactions are made per day, because FAMAGA supplies all over the globe Germany, United Kingdom, Slovenia, Nepal, Bolivia, Cambodia, Cape Verde, Armenia, Bahamas, Bhutan, Canada, Costa Rica, Ireland, Malaysia, Russia, Mauritius, Tunisia, Rwanda, Mexico, Chile, United Arab Emirates, Latvia, Guyana, Chad, Albania, Burkina Faso, Andorra, Angola, Qatar, Samoa, Turkey, Philippines, Greece, Mozambique, Serbia, Brunei, Madagascar, Eswatini, Georgia, Macedonia, Afghanistan, Djibouti, Sweden, Mali. A well-elaborated logistics chains and a partnership network allow us to send our units anywhere in the earth with no delay without undermining product quality.
A special source of pride for FAMAGA is its staff members, each of whom contributes to common cause. We propose into our team only professionals, who already have experience in the range of machine made streamlined equipment.
All items from FAMAGA are ensured - we are responsible for the aftereffect of our work. Nowadays, more than 10 million units of products have been provided, and this amount is increasing every day. We are glad that purchasers choose FAMAGA again and again, and we are eager to make more developed and technologically modern industrial equipment so as keep on top of it.
To consult or make a request, phone us or write to the online chat on our site. You can also dispatch a list of the needful equipment to the email of firm - we will contact you ourselves with a prepared commercial proposal from FAMAGA.
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Rated operating distance | 5 mm | |
Installation | non-flush | |
Assured operating distance | 0 ... 4.05 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.85 | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Switching frequency | 0 ... 3000 Hz | |
Hysteresis | typ. % | |
Suitable for 2:1 technology | yes , Reverse polarity protection diode not required | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | &le, 1 mA | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
MTTFd | 11774 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
Approvals and certificates | ||
EAC conformity | TR CU 012/2011 | |
UL approval | cULus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le,36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 5 m | |
Core cross-section | 0.34 mm2 | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | PVDF | |
Degree of protection | IP68 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
Data for application in connection with hazardous areas | ||
Equipment protection level | Gb , Gc (ic) , Da , Mb | |
Equipment protection level Gb | ||
Type of protection | intrinsic safety | |
CE marking | [*PD-Z02585A*] | |
Certificates | ||
Appropriate type | NJ 5-11-N... | |
ATEX certificate | PTB 00 ATEX 2048 X | |
ATEX marking | II 2G Ex ia IIC T6&hellip,T1 Gb | |
Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
IECEx certificate | IECEx PTB 11.0037X | |
IECEx marking | Ex ia IIC T6...T1 Gb | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
Effective internal capacitance | max. 45 nF A cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µ,H A cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW , T6 : 72 °C (161.6 °F) T5 : 87 °C (188.6 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW , T6 : 65 °C (149 °F) T5 : 80 °C (176 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW , T6 : 42 °C (107.6 °F) T5 : 57 °C (134.6 °F) T4 : 82 °C (179.6 °F) T3 : 82 °C (179.6 °F) T2 : 82 °C (179.6 °F) T1 : 82 °C (179.6 °F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW , T6 : 26 °C (78.8 °F) T5 : 41 °C (105.8 °F) T4 : 63 °C (145.4 °F) T3 : 63 °C (145.4 °F) T2 : 63 °C (145.4 °F) T1 : 63 °C (145.4 °F) | |
Equipment protection level Gc (ic) | ||
Type of protection | intrinsic safety | |
CE marking | [*PD-Z02586A*] | |
Certificates | ||
ATEX certificate | PF 13 CERT 2895 X | |
ATEX marking | II 3G Ex ic IIC T6&hellip,T1 Gc | |
Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
Effective internal capacitance | max. 45 nF A cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µ,H A cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 20 V , Ii = 25 mA , Pi = 34 mW , T6 : 55 °C (131 °F) T5 : 55 °C (131 °F) T4 : 55 °C (131 °F) T3 : 55 °C (131 °F) T2 : 55 °C (131 °F) T1 : 55 °C (131 °F) at Ui = 20 V , Ii = 25 mA , Pi = 64 mW , T6 : 55 °C (131 °F) T5 : 55 °C (131 °F) T4 : 55 °C (131 °F) T3 : 55 °C (131 °F) T2 : 55 °C (131 °F) T1 : 55 °C (131 °F) at Ui = 20 V , Ii = 52 mA , Pi = 169 mW , T6 : 32 °C (89.6 °F) T5 : 32 °C (89.6 °F) T4 : 32 °C (89.6 °F) T3 : 32 °C (89.6 °F) T2 : 32 °C (89.6 °F) T1 : 32 °C (89.6 °F) at Ui = 20 V , Ii = 76 mA , Pi = 242 mW , T6 : 16 °C (60.8 °F) T5 : 16 °C (60.8 °F) T4 : 16 °C (60.8 °F) T3 : 16 °C (60.8 °F) T2 : 16 °C (60.8 °F) T1 : 16 °C (60.8 °F) | |
Equipment protection level Da | ||
Type of protection | intrinsic safety | |
CE marking | [*PD-Z02585A*] | |
Certificates | ||
Appropriate type | NJ 5-11-N... | |
ATEX certificate | PTB 00 ATEX 2048 X | |
ATEX marking | II 1D Ex ia IIIC T135°C Da | |
Standards | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
IECEx certificate | IECEx PTB 11.0037X | |
IECEx marking | Ex ia IIIC T135°C Da | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
Effective internal capacitance | max. 45 nF A cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µ,H A cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 82 °C (179.6 °F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 63 °C (145.4 °F) | |
Equipment protection level Mb | ||
Certificates | ||
Appropriate type | NJ 5-11-N... | |
IECEx certificate | IECEx PTB 11.0037X | |
IECEx marking | Ex ia I Mb | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
Effective internal capacitance | max. 45 nF A cable length of 10 m is considered. | |
Effective internal inductance | max. 50 µ,H A cable length of 10 m is considered. | |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 82 °C (179.6 °F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 63 °C (145.4 °F) | |
General information | ||
Use in the hazardous area | see instruction manuals |