Name
NCN4-12GM40-E2-3G-3D
Part number
310841
Type
Inductive sensor
Description
Inductive sensor NCN4-12GM40-E2-3G-3D
Stock availability:
On request
If you are questing Pepperl+Fuchs NCN4-12GM40-E2-3G-3D 310841, communicate with FAMAGA, the world's key company of mechanized equipment. Our company has worked for more than ten years - these are ages of experience, which are illustrated in the quality of goods and personalseparate attention to each buyer. We cherish everyone, who worked with us - thus, our regular customers get the most helpful purchase terms and discounts on the machine made streamlined equipment market. Now, there are more than 4 thousand such customers, and we constantly arrange new agreements. More than 700 contracts are concluded per day, because FAMAGA works all over the earth Germany, United Kingdom, Botswana, Namibia, Australia, Zambia, United States, Myanmar, Slovenia, Kyrgyzstan, Antigua and Barbuda, Senegal, Mozambique, Sierra Leone, Bulgaria, Malta, Belgium, Haiti, Turkmenistan, Macedonia, Czech Republic, Bosnia and Herzegovina, Serbia, Luxembourg, Niger, Equatorial Guinea, Uganda, Kiribati, Panama, Brazil, Philippines, Ecuador, Lithuania, Swaziland, Benin, Austria, Kazakhstan, Mali, Uruguay, New Zealand, Estonia, Norway, Pakistan, Central African Republic, Argentina, North Korea, Mexico. A well-shaped logistics network and a partnership network help us to dispatch our products anywhere in the globe promptly without compromising product quality.
A special source of pride for FAMAGA is its personnel, each of whom contributes to our work. We accept into our team only professionals, who already have experience in the direction of factory-made equipment.
All outcomes from FAMAGA are guaranteed - we are responsible for the result of our work. At this moment, more than 10 million units of products have been supplied, and this bulk is growing every day. We are happy that buyers choose FAMAGA again and again, and we are glad to make more exceptional and technologically advanced industrial equipment so as to stay on the top.
To consult or book, contact us or send a message to the online chat on our site. You can also forward a list of the desirable equipment to the email of corporation - we will contact you ourselves with a made commercial proposal from FAMAGA.
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 4 mm | |
Installation | non-flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 3.24 mm | |
Actual operating distance | 3.6 ... 4.4 mm typ. 4 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.36 | |
Reduction factor r304 | 0.74 | |
Reduction factor rBrass | 0.45 | |
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 0 ... 2200 Hz | |
Hysteresis | 3 ... 15 typ. 7 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le, 3 V | |
Voltage drop at IL | ||
Voltage drop IL = 200 mA, switching element on | 1 ... 2 V typ. 1.5 V | |
Operating current | &le, 200 mA | |
Off-state current | 0 ... 0.5 mA typ. 0.01 mA | |
No-load supply current | &le, 15 mA | |
Time delay before availability | &le, 100 ms | |
Switching state indicator | LED, yellow | |
Functional safety related parameters | ||
MTTFd | 1517 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
CCC approval | CCC approval / marking not required for products rated &le,36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 2 m | |
Core cross-section | 0.34 mm2 | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | PBT | |
Degree of protection | IP66 / IP67 | |
Cable | ||
Cable diameter | 4.6 mm ± 0.2 mm | |
Bending radius | > 10 x cable diameter | |
Data for application in connection with hazardous areas | ||
Equipment protection level | Gc (nA) , Dc | |
Equipment protection level Gc (nA) | ||
Type of protection | n | |
CE marking | [*PD-Z02586A*] | |
Certificates | ||
ATEX certificate | PF15CERT3754X | |
ATEX marking | II 3G Ex nA IIC T6 Gc | |
Standards | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
Surge protection | The protection against transient overvoltage with amplitude U is realized. U = 500 V at 1.2/50 µ,s, 500 &Omega, | |
Possible characteristics | maximum operating voltage UBmax , maximum load current ILmax , minimum series resistance RV , maximum analog output voltage UAmax , maximum analog output current IAmax | |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at UBmax = 30 V , IL = 200 mA : 43 °C (109.4 °F) at UBmax = 30 V , IL = 100 mA : 50 °C (122 °F) at UBmax = 30 V , IL = 50 mA : 53 °C (127.4 °F) | |
Equipment protection level Dc | ||
Type of protection | Protection by enclosure tc | |
CE marking | [*PD-Z02586A*] | |
Certificates | ||
ATEX certificate | PF15CERT3774X | |
ATEX marking | II 3D Ex tc IIIC T80°C Dc | |
Standards | EN 60079-0:2012+A11:2013 , EN 60079-31:2014 | |
Possible characteristics | maximum operating voltage UBmax , maximum load current ILmax , minimum series resistance RV , maximum analog output current IAmax , maximum analog output voltage UAmax | |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at UBmax = 30 V , IL = 200 mA : 43 °C (109.4 °F) at UBmax = 30 V , IL = 100 mA : 50 °C (122 °F) at UBmax = 30 V , IL = 50 mA : 53 °C (127.4 °F) | |
General information | ||
Scope of delivery | 2 self locking nuts in scope of delivery | |
Use in the hazardous area | see instruction manuals |