Signal Converter KFD2-UT2-2-1 Pepperl+Fuchs 248763
Signal Converter KFD2-UT2-2-1 Pepperl+Fuchs 248763

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

KFD2-UT2-2-1 248763 Pepperl+Fuchs Signal Converter

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KFD2-UT2-2-1

Part number

248763

Type

Signal Converter

Description

Universal Temperature Converter KFD2-UT2-2-1

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KFD2-UT2-2-1 248763

This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device converts the signal of a resistance thermometer, thermocouple, or potentiometer to a proportional output voltage. The device can also be configured as a signal splitter. The removable terminal block K-CJC-** is available as an accessory for internal cold junction compensation of thermocouples. A fault is signalized by LEDs acc. to NAMUR NE44 and a separate collective error message output. The device is easily configured by the use of the PACTware configuration software. For additional information, refer to the manual and www.pepperl-fuchs.com.

Features KFD2-UT2-2-1 248763

Product Description
Voltage output 0/1 V ... 5 V
General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 14+, 15- or power feed module/Power Rail
Rated voltage20 ... 30 V DC
Ripplewithin the supply tolerance
Power dissipation/power consumption&le, 0.8 W / 0.8 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3, 4, 5, 6
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760)
Measuring currentapprox. 200 µ,A with RTD
Types of measuring2-, 3-wire connection
Lead resistancemax. 50 &Omega, per line
Measurement loop monitoringsensor breakage, sensor short-circuit
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001)
Cold junction compensationexternal and internal
Measurement loop monitoringsensor breakage
Potentiometer0 ... 20 k&Omega, (2-wire connection), 0.8 ... 20 k&Omega, (3-wire connection)
Voltageselectable within the range -100 ... 100 mV
Input resistance&ge, 1 M&Omega, (-100 ... 100 mV)
Output
Connection sidecontrol side
Voltage output0 ... 5 V or 1 ... 5 V , output resistance: &le, 5 &Omega, , load: &ge, 10 k&Omega,
Connectionoutput I: terminals 7-, 8+ output II: terminals 10-, 11+
Fault signaldownscale 0 V or 0.5 V, upscale 5.375 V
Transfer characteristics
Deviation
After calibrationPt100: ± (0.06 % of measurement value in K + 0.1 K (4-wire connection)) thermocouple: ± (0.05 % of measurement value in °C + 1 K (1.2 K for types R and S)) this includes ± 0.8 K error of the cold junction compensation mV: ± 50 µ,V potentiometer: ± 0.05 % of full scale, (excludes errors due to lead resistance) output: 1 to 5 V output: ± 4 mV from 0 to 103.1 % of span, 0 to 5 V output: ± 4 mV from 0.3 to 102.5 % of span
Influence of ambient temperaturedeviation of CJC included: Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K &Delta,Tamb*) thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K &Delta,Tamb*) mV: ± (0.01 % of measurement value + 0.006 % of span)/K &Delta,Tamb*) potentiometer: ± 0.006 % of span/K &Delta,Tamb*) *) &Delta,Tamb = ambient temperature change referenced to 23 °C (296 K)
Influence of supply voltage< 0.01 % of span
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Galvanic isolation
Input/Other circuitsbasic insulation according to IEC 61010-1, rated insulation voltage 300 Veff
Output/supply, programming inputfunctional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided.
Indicators/settings
Display elementsLEDs
Configurationvia PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 130 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- FDT framework PACTware 5.X - device type manager DTM Interface Technology - power feed module KFD2-EB2(.R4A.B)(.SP) - universal power rail UPR-03(-M)(-S) - profile rail K-DUCT-GY(-UPR-03)