We are not the manufacturer, authorised distributor or authorised representative of the IFM brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.
Manufacturer
IFM
Country
Germany
Part number
SL0101
Description
Airflow monitor for use in ventilation systems in building automation
Stock availability:
On request
Appendix | |||||
---|---|---|---|---|---|
Measured medium temperature [°C] | -10…50 | < /tr>||||
Pressure strength [bar] | 1 | ||||
Electronic data | |||||
Operating voltage [V] | 80…250 AC / 90…250 DC | ||||
Min. insulation resistance [M?] | 100, (500 V DC) | ||||
Reverse polarity protection | none | ||||
Power-on delay time [s] | 60 | ||||
Inputs/outputs | |||||
Number of inputs and outputs | Number of relay outputs: 1 | ||||
Outputs | |||||
Output signal | Switching signal | ||||
Number of relay outputs | 1 | ||||
Contact load | 3 A (30 V DC / 250 V AC) | ||||
Switching function flow rate control | with flow relay closes | ||||
Short circuit protection | none | ||||
Overcurrent protection | none | ||||
Measuring/setting range | |||||
Gases | |||||
Parameter setting within [cm/s] | 100…1000 | ||||
Max. sensitivity [cm/s] | 100…400 | ||||
Accuracy/error | |||||
Max temperature gradient (rate of change of medium temperature) [K/min] | 5 | ||||
Response time | |||||
Response time [s] | 3…60 | ||||
Gases | |||||
Response time [s] | 3…60 | ||||
Software / Programming | |||||
Setting the switching point | with potentiometer | ||||
Operating conditions | |||||
Ambient temperature [°C] | -10…50 | ||||
Max. permissible relative humidity [%] | 90 | ||||
Degree of protection | IP 65 | ||||
MTTF [years] | 747 | ||||
Mechanical data< /th> | |||||
Weight [g] | 208 | ||||
Dimensions [mm] | O 23 / L = 142 | ||||
Material | Body: PBT (polybutylene terephthalate), sensing surface: titanium | ||||
Body materials in contact with meas. medium | PBT (polybutylene terephthalate), titanium | ||||
Process connection | O 23 mm | ||||
Displays / Controls | |||||
Display |
| ||||
Electrical connection | |||||
Required protection | miniature fuse IEC60127-2 sheet 1, ? 5 A, fast response | ||||
Accessories | |||||
Accessories (supplied) |
| ||||
Notes | |||||
Notes |
| ||||
Packing quantity | 1 piece | ||||
electrical connection | |||||
Connection | Cable: 2 m, PVC, 4 x 0.5 mm? |